5.3.10 Submenu “Opt. Outputs Settings”
Two sets of optically-isolated digital outputs are provided to actuate user-sup-
plied equipment. These are programmable via digital interface or LCD/Keypad
such that the outputs can be made to switch when a specified event occurs (e.g.
when a Low or High Flow Alarm limit is exceeded, when the Totalizer reaches a
specified value), or it may be directly controlled by user.
The user can configure each optical output action from 9 different options:
Disabled: No Action.
(Output is not assigned to any events and is not energized).
Low Flow Alarm.
High Flow Alarm.
Range between H&L Flow Alarm settings.
Totalizer #1 reading exceed set limit.
Totalizer #2 reading exceed set limit.
Pulse Output function.
Diagnostic: Output will be energized when any of the Diagnostic or
System events are active.
Manual On Control: Output will be energized until Disabled option is
selected.
By default both optically-isolated outputs are disabled.
NOTE: Optically-isolated outputs are accessible via screw terminal
header J1 and require application of external DC voltage across
terminals. See Paragraph 4.5 for proper wiring connections.
,