84
COMMAND
NAME
DESCRIPTION
NO.
COMMAND SYNTAX
COMMAND
ARGUMENT 1
ARGUMENT 2 ARGUMENT 3 ARGUMENT 4 RESPONSE
Pressure
Alarms**
Sets / reads the status of the
pressure alarms.
Note: High and Low limits have
to be entered in the Pa units.
High alarm value has to be
more than Low alarm value.
Alarm conditions:
Pressure > High Limit = H
Pressure. < Low Limit = L
Low < Press. < High = N
10 PA H
(high press. limit)
<Value>
(0–Max.Press.)
PAH:<Value [PA]>
L
(low press. limit)
<Value>
(0-Max.Press.)
PAL:<Value [Pa]>
A
(action delay in
seconds)
<Value> (0-3600
sec.)
PAA:<Value [sec]>
E
(enable alarm)
PA:E
D
(disable alarm)*
PA:D
R (read
current status)
PAR:N (no alarm)
PAR:H (high alarm)
PAR: L (low alarm)
S (Read
current settings)
PAS:M,L,H,D,B where:
M – mode (E/D)
L – Low settings (Pa)
H – High settings (Pa)
D – Action Delay (sec)
B – Latch mode (0-1)
B Block (Latch)
mode
<Value>
(0-disabled*)
(1-enabl’d )
PAB:<Value> where:
Value = 0 – 1